Testo 324 pressure gauge and leak detector
The testo 324 pressure gauge and gas leak detector allows for pressure measurements, DVGW-approved leak detection for all gas pipeline tests, tightness and maintenance checks.

The testo 324 pressure/leak detector can be used for the following applications
- Leak tightness checks on gas pipes (leak tightness check and load test according to TRGI 2008 and DVGW G 5952)
- Serviceability checks according to TRGI 2008 on gas pipes
- Pressure tests on water pipes (drinking water according to ZVSHK EN 806-4, waste water according to DIN EN 1610)
- Leak tightness checks on liquid gas pipes according to TRF 2012
- Gas pressure regulator inspections
- Pipe volume measurements
- Further applications including temperature measurements at radiators and pressure measurements at burners (die pressure, gas flow pressure…)
| Temperature – NTC | |
|---|---|
| Measuring range | -20 to +100 °C |
| Temperature – TC Type K (NiCr-Ni) | |
|---|---|
| Measuring range | -40 to +600 °C |
| Accuracy | ±0.5 °C or ±0.5 % |
| Absolute Pressure | |
|---|---|
| Measuring range | 600 to 1150 hPa |
| Accuracy | ±3 hPa |
| Overload | to 1200 hPa |
| Leakage measurement | |
|---|---|
| Measuring range | 0 to 10 l/h |
| Accuracy | ±0.2 l/h or ±5 % of mv |
| Resolution | 0.1 l/h |
| Pressure measurement | |
|---|---|
| Measuring range | 0 to 1000 hPa |
| Accuracy | ±0.5 hPa or ±3 % of mv |
| Pressure measurement (external probe) | |
|---|---|
| Measuring range | 0 to 25 bar |
| Accuracy | ±0.6 % fs (0 to 10 bar) ±0.6 % fs (> 10 to 25 bar) |
| General technical data | |
|---|---|
| Overload | 1200 hPa |
| Weight | 1070 g |
| Dimensions | 270 x 90 x 75 mm |
| Operating temperature | +5 to +40 °C |
| Protection class | IP40 acc. to EN 60529 |
| Additional probe sockets | 2 Hirschmann sockets for connecting pressure and temperature probes |
| Gas connections | 2 pressure connections DN 5 |
| DVGW permit according to 5925 | Instrument class L up to volume = 200 litres |
| Display type | Colour display, presentation of graphic curves |
| Data transfer | USB, IRDA, Bluetooth® (option) |
| Battery life | approx. 5 h measurement time, mains operation possible |
| Storage temperature | -20 to +50 °C |
| Pipe volume calculation | |
|---|---|
| Measuring range | max. 1200 l |
| Accuracy | ±0.2 or ±5 (1 to 200 l)F |